FD-0.6/1 KV-CV-SWA
0.6/1 KV 90°C CROSS-LINKED POLYETHYLENE INSULATED PVC SHEATHED, WITH GALVANIZED STEEL WIRES ARMORED POWER CABLE
Medium Voltage Power Cables for between Tranformer amd MDB, Cable is easy to bend and easy to work.
FD-0.6/1 KV-CV-SWA
0.6/1 KV 90°C CROSS-LINKED POLYETHYLENE INSULATED PVC SHEATHED, WITH GALVANIZED STEEL WIRES ARMORED POWER CABLE
Medium Voltage Power Cables for between Tranformer amd MDB, Cable is easy to bend and easy to work.
60227 IEC 10 NYY
300/500 V 70°C SOLID AND STRANDED CONDUCTOR PVC INSULATED
Exposed installation, or in raceway, wet or dry location or direct burial in ground.
60227 IEC 53 VCT or 60227 IEC 53 VCT-G
300/500 V 70°C FLEXIBLE CONDUCTOR PVC INSULATED AND SHEATHED, ROUND TYPE
Round type with Ground-Wire for mobile-electrical equipment used in mines, factories, farm or household appliances.
60227 IEC 52 VCT
300/300 V 70°C FLEXIBLE CONDUCTOR PVC INSULATED AND SHEATHED, ROUND TYPE
Round type for mobile-electrical equipment used in mines, factories, farm or household appliances.
300/500 V 70°C SOLID AND STRANDED CONDUCTOR PVC INSULATED AND SHEATHED WITH GROUND, FLAT TYPE
Conductor |
Solid and stranded annealed copper, Size 1 mm² up to 16 mm² |
---|---|
Ground wire |
Solid and stranded annealed copper, Size 1 mm² up to 16 mm² |
Insulation |
Polyvinyl chloride (PVC/C) 2 Core : Blue and Brown Ground-Cores : Green/Yellow |
Core identification | White polyvinyl chloride (PVC/ST4) |
Outer sheath | Maximum conductor temperature 70°C |
Classification |
Circuit voltage not exceeding 300/500 Volts 300 Volts between Line-to-Earth 500 Volts between Line-to-Line |
Testing voltage | 2,000 Volts |
Reference standard | TIS 11 Part 101-2553, Table 1 |
300/500 V 70°C SOLID AND STRANDED CONDUCTOR PVC INSULATED AND SHEATHED, FLAT TYPE
Conductor |
Solid and stranded annealed copper, Size 1 mm² up to 16 mm² |
---|---|
Insulation |
Polyvinyl chloride (PVC/C) 2 Core : Blue and Brown |
Core identification | White polyvinyl chloride (PVC/ST4) |
Outer sheath | Maximum conductor temperature 70°C |
Classification |
Circuit voltage not exceeding 300/500 Volts 300 Volts between Line-to-Earth 500 Volts between Line-to-Line |
Testing voltage | 2,000 Volts |
Reference standard | TIS 11 Part 101-2553, Table 1 |
60227 IEC 02 THW (f)
450/750 V 70°C FLEXIBLE CONDUCTOR PVC INSULATED , SINGLE CORE
Indoor fixed installation in dry location, for electrical panels connection or for electrical apparatus.
Conductor | Flexible annealed copper wire Size 1.5 mm² up to 240 mm² |
---|---|
Insulation | Polyvinyl chloride (PVC/C) |
Core identification | Single – core : Any color |
Outer sheath | Maximum conductor temperature 70°C |
Classification |
Circuit voltage not exceeding 450/750 Volts 450 Volts between Line-to-Earth 750 Volts between Line-to-Line |
Testing voltage | 2,500 Volts |
Reference standard | TIS 11 Part 3-2553, Table 3 |
60227 IEC 01 THW
450/750 V 70°C SOLID AND STRANDED CONDUCTOR PVC INSULATED, SINGLE CORE
Building wiring for installation on insulator or in race way, dry location.
Conductor | Solid and stranded annealed copper Size 1.5mm² up to 400 mm² |
---|---|
Insulation | Polyvinyl chloride (PVC/C) |
Core identification | Single – core : Any color |
Classification | Maximum conductor temperature 70°C |
Classification |
Circuit voltage not exceeding 450/750 Volts 450 Volts between Line-to-Earth 750 Volts between Line-to-Line |
Testing voltage | 2,500 Volts |
Reference standard | TIS 11 Part 3-2553, Table 1 |